Source & Tap

New Jersey tap water / Water systems

Middlesex Water Company: 2025 water quality report results

In its 2025 water quality report, the Middlesex Water Company reported PFOA at 2.9 ppt and PFOS at 1.8 ppt (highest compliance result). PFOA and PFOS are below both the New Jersey and federal limits. Lead at the 90th percentile of home taps: 1 ppb. Hardness: 157 mg/L (hard).

Public water system NJ1225001. Read the utility's 2025 report; every value below was checked against it.

2025 results against New Jersey and federal limits

PFOA Perfluorooctanoic acid2.9 ppt

Highest compliance result in the 2025 report; range in the report: not detected to 7 ppt

Below both limits

PFOS Perfluorooctane sulfonic acid1.8 ppt

Highest compliance result in the 2025 report; range in the report: not detected to 5 ppt

Below both limits

Each bar shows the highest compliance result reported for this system, in parts per trillion (ppt), against both limits. The darker band is the range of results the report lists; the status compares the reported value, not the top of the range, with the limits.

Middlesex Water Company: values in the 2025 water quality report, with New Jersey and federal limits
MeasureReportedNJ limitFederal limitStatus
PFOAPerfluorooctanoic acid2.9 pptRange in the report: not detected to 7 ppt14 ppt4 pptBelow both limits
PFOSPerfluorooctane sulfonic acid1.8 pptRange in the report: not detected to 5 ppt13 ppt4 pptBelow both limits
Lead90th percentile of home taps1 ppbThe report gives the 90th percentile without a range, sampling year or number of sites.Action level 15 ppb (10 ppb from November 2027)Below action level
Arsenic1 ppbHighest compliance result, range ND to 1 ppb, 20255 ppb10 ppbBelow both limits
1,2,3-Trichloropropane20 pptHighest compliance result, range ND to 20 ppt, 20250.03 ppbNoneBelow New Jersey limit
ChlorideSecondary standard48 ppmAverage, range 43 to 52 ppm, 2025250 ppm recommended upper limitNot enforceable250 ppmSecondary standard, not enforceableBelow recommended limit
SodiumSecondary standard35 ppmAverage, range 30 to 39 ppm, 202550 ppm recommended upper limitNot enforceableNoneBelow recommended limit
Hardness157 mg/L (9.2 gpg)The utility's report lists an average of 157 mg/L (2025).250 mg/L recommended upper limitFor taste and appearance; not enforceableNoneClass: hardA description, not a limit comparison

The report doesn't say whether that figure is a single result or a running annual average.

New Jersey sets its own limits for arsenic (stricter than the federal one) and 1,2,3-trichloropropane (no federal limit); its sodium and chloride limits are recommended upper limits, not enforceable. Federal limits as of November 2026.

According to EPA, lead gets into drinking water when plumbing that contains lead corrodes, and where a home has a lead service line, that pipe is typically the largest source. So a home's own tap can differ from the system-wide 90th percentile.

Other PFAS detected in EPA's nationwide testing (UCMR 5), not charted because the figure isn't a compliance result: PFBS, PFHxA, PFBA and PFPeA.

EPA kept its 4 ppt limits for PFOA and PFOS. Utilities must meet them by 2029; EPA has proposed letting systems request until 2031. In May 2026, EPA proposed withdrawing its national limits for PFNA, PFHxS, GenX (HFPO-DA) and a combined limit for PFAS mixtures. The proposal isn't final yet; EPA plans to decide in 2026. New Jersey's own PFNA limit is unaffected. (Status as of November 2026.)

Compare the Middlesex Water Company with other New Jersey water systems in one table of 2025 PFAS results, or see hardness across the same systems.

Choosing a water filter

The utility's PFAS compliance results were below the federal limits. If you still want a filter, or you're concerned about lead from your home's pipes, look for one certified to NSF/ANSI Standard 53 for the contaminant you care about.

Towns served by the Middlesex Water Company

Water sources

Surface water is obtained from the Delaware and Raritan Canal, supplemented by the Round Valley and Spruce Run Reservoir Systems, and provides 72 percent of the water distributed by the system. The remainder comes from wells in the Brunswick Aquifer (21 percent) and purchased water (7 percent) from New Jersey American Water-Raritan System.

The report says this system buys water from New Jersey American Water, Raritan system.

Source. 2025 water quality report, Middlesex Water Company. Also: EPA Safe Drinking Water Information System; EPA UCMR 5.

Checked against the original report in November 2026. See how we check the data. Found an error? Tell us.